Search
Close this search box.

RAPIX DALI-2 24m IP65 Long Range Occupancy / Light Level Sensor

Features

  • Detection range: up to 24 metre diameter at 10 m ceiling height
  • Only 4 mA current drawn from DALI
  • Rated to IP65
  • Generous terminal sizes for easy DALI connection, allowing loop-in / loop-out
  • Large cable strain relief for easy installation
  • Transparent wiring cover for easy inspection of the cable connection while preserving safety isolation
  • Up to 20 sensors can be installed per DALI line
  • Light Level measurement 0 – 65,000 lux
  • External input suits all switch types and voltage free contacts of other movement sensors
  • Bright LED indicator at lens for easy visual identification / location of an installed sensor
  • Bright LED indicator at rear terminal block, allows easy verification of DALI connectivity during installation
  • Configured using the FREE RAPIX Addressing and RAPIX Integrator software tools

Description

The RAPIX DALI IP65 Long Range Occupancy / Light Level Sensor is a DALI Application Controller with PIR movement sensing, light level sensing, and a voltage-free input.

The RAPIX Long Range Occupancy Sensor allows all common movement / occupancy operations as well as light level sensing and light level maintenance. Switching and control functions are available using the voltage-free input.

This sensor can act as a miniature DALI Application Controller. Multiple sensors can easily be used to expand coverage to larger areas. For further scalability, the sensor can be mixed on a line with RAPIX eHubs or the RAPIX Universal Switch Input. For an installation that spans multiple DALI lines, scaling up is easy using the RAPIX Zone Controller.

The sensor can be enabled or disabled based on a DALI short address, or by system rules managed by a Zone Controller.

Like other RAPIX Application Controllers a Zone approach is used. Zones are made up of a mix of DALI Short Addresses, Groups, or the DALI broadcast.

Functions available include occupancy (unconditional), occupancy (when light level above a limit), vacancy, light level maintenance and light level switch.

When turning a Zone off, the occupancy / timer functions include fade off, fade to a dwell level before turn off, or pulse before turn off. The sensor can also keep an area on while adjacent areas are on, allowing easy setup of corridor or exit path lighting.

The separate switch input allows connection of voltage-free toggle switches or common push-style momentary switches. Alternatively the voltage-free contacts of a separate low-cost movement sensor can be connected to this input. This input has over 20 possible functions that can be selected. If a suitable function is not supported, Ozuno can create a custom function that is instantly deployed using RAPIX Addressing or RAPIX Integrator software.

This sensor also supports sophisticated scene control, and allows easy scale up where additional sensors can act as slaves to a master sensor.

Documentation

Data Sheet

Installation Guide

Brochure