A high quality universal input power supply with 12 V dc, 1 A output.
This power supply can be used to power the RAPIX DALI-2 Zone Controller and RAPIX DALI Ethernet Interface.
We suggest power supplies are loaded to no more than 75% of its capacity – this allows a little headroom, for example to handle peak currents when a load starts. Therefore, use a maximum of 750 mA of active load currents.
Pay attention to peak (start-up) currents and try to avoid exceeding 80% of the rated capacity.
For example:
Product | Power | Number | Total Power | OK |
---|---|---|---|---|
Zone Controller | 200 mA | 3 | 600 mA | YES |
Ethernet Interface | 100 mA (active) 200 mA (peak) | 4 | 400 mA (active) 800 mA (peak) | YES |
Zone Controller + Ethernet Interface | 200 mA + 200 mA (peak) | 2 + 2 | 600 mA (active) 800 mA (peak) | YES |
Zone Controller + Ethernet Interface | 200 mA + 200 mA (peak) | 3 + 1 | 700 mA (active) 800 mA (peak) | YES |
Zone Controller + Ethernet Interface | 200 mA + 200 mA (peak) | 1 + 3 | 500 mA (active) 800 mA (peak) | YES |
Zone Controller + Ethernet Interface | 200 mA + 200 mA (peak) | 2 + 3 | 700 mA (active) 1000 mA (peak) | NO (Excessive start-up current) |
Sign up to keep up to date on our latest product and software developments.
Register for news and notification of updates
Why Register? Registering makes it easier to inform our customers and users about new updates and features.
We won’t fill your inbox with spam emails and we will never sell any mailing lists.